Example application · Lakewood, Ohio · R1H
A filled, illustrative application packet: owner-builder affidavit, zoning worksheet, ABR narrative, before/after plates, and A/S/E/P/M/LS drawings. Use it as a shape, not as a sealed set.
| Owner | [OWNER NAMES] — owner-builder |
| Address / parcel | [ADDRESS], Lakewood, OH 44107 · [PARCEL] |
| Zone / lot | R1H · 50'-0" × 175'-0" = 8,750 SF |
| Existing footprint | 1,850 SF (21.1% of lot; 35% max) |
| Proposed footprint | 1,850 SF (no increase; second floor over existing wing) |
| Total lot coverage | 2,050 SF (23.4%; 85% max) |
| Rear yard | 38'-0" existing / 38'-0" proposed; 40'-0" required → variance |
| Side yards | 7'-6" / 7'-6"; sum 15'-0" (5' min each; 15' sum) |
| Height | 18'-0" existing / 27'-0" proposed; 35'-0" max |
| Scope | Remove sloped/multi-sloped roof; new 400 SF second floor; bedroom 12'×16'; bath 8'×10'; closet 6'×8'; stair/hall 4'×20'; new roof; MEP; finishes. |
| Designer | [PE], Ohio PE [LICENSE NO.] |
| Structural PE | [NAME], Ohio PE [LICENSE NO.] |
| Permit type | Building permit — residential addition |
| Property class | 1-family dwelling |
| Scope | Second-floor addition over existing one-story rear wing; remove existing roof; new floor, walls, roof, stair, bedroom, bathroom; electrical, plumbing, HVAC; insulation and finishes. |
| Contractor | Owner-builder (affidavit attached) |
| Valuation | $[____] (materials + paid labor; confirm owner-labor treatment with the city) |
| ABR | Required — exterior elevation change; approval attached |
| Historic | [Not in HPD/HP / confirmation attached] |
| Flood | [Zone X / confirmation attached] |
| Energy | 2018 IECC compliance attached |
| Structural | Sealed calculations and letter attached |
| Electrical | Load calculation and panel schedule attached |
| Plumbing | Plan and riser attached |
| HVAC | Manual J and duct layout attached |
TEMPLATE — REPLACE BRACKETS WITH REAL DATA; USE LAKEWOOD’S CURRENT FORM.
| Item | Existing | Proposed | Limit / code |
|---|---|---|---|
| Principal footprint | 1,850 SF | 1,850 SF | 3,062.5 SF max (35%) |
| Total lot coverage | 2,050 SF | 2,050 SF | 7,437.5 SF max (85%) |
| Rear yard | 38'-0" | 38'-0" | 40'-0" min — nonconforming |
| Side yards | 7'-6" / 7'-6" | 7'-6" / 7'-6" | 5'-0" each; 15'-0" sum |
| Height | 18'-0" | 27'-0" | 35'-0" max |
| Front yard | [__] | [__] | Building Line Map / average |
Nonconformity note: the existing rear wing is 38'-0" from the rear lot line; R1H requires 40'-0". The proposed second floor is directly above the existing footprint and does not extend the rear wall. The owner requests the City’s written determination whether this increases the nonconformity under LCO §1149.04; if it does, the BZA variance narrative applies.
Project: 400 SF second-floor addition over existing one-story rear wing. Existing: one-story rear wing with sloped/multi-sloped roof; [siding]; [roof]; [windows]. Proposed: new second-floor volume within the existing footprint; new [gable/hip] roof at [__] pitch tying into the existing ridge/valley; [siding], [roofing], [windows], [trim], [gutters]; colors [body/trim/roof]. Height: 27'-0"; rear yard: 38'-0"; side yards: 7'-6"/7'-6". Compatibility: massing steps back from the existing ridge; window rhythm and materials match the house and block. Photos: front/side/rear/context attached.
Before — illustrative massing. Replace with real rear/side/context photos.
After — illustrative massing. Replace with real photos of the completed or proposed volume.
PHOTO LOG: FRONT, SIDE, REAR, CONTEXT, ROOF BEFORE, ROOF AFTER, ADJACENT HOUSES.
Cover sheet: project data, code matrix, sheet index, general notes.
Existing conditions: 50 × 175 lot, 7'-6" side yards, 38'-0" rear yard, one-story rear wing with multi-slope roof.
Proposed 20 × 20 second floor: bedroom, bath, closet, stair/hall, egress window.
Roof plan: slopes, ridge, valleys, ice barrier, flashing, ventilation, gutters.
Section: existing first floor, new floor framing, new second floor, new roof, insulation/air sealing.
S1.0: new footings, beam, columns, joists, load path, shoring and inspection notes. Seal by Ohio structural PE.
E1.0: lighting, receptacles, switches, smoke/CO, bath GFCI, panel location.
| Circuit | Description | Amps | Protection | Wire |
|---|---|---|---|---|
| 1 | Bedroom receptacles | 15 | AFCI | 14/2 |
| 2 | Bedroom lighting | 15 | AFCI | 14/2 |
| 3 | Bath receptacles | 20 | GFCI | 12/2 |
| 4 | Bath lighting/exhaust | 15 | AFCI | 14/2 |
| 5 | Smoke/CO | 15 | AFCI | 14/3 |
| 6 | Spare | 20 | — | 12/2 |
Load summary: general lighting 1,200 VA; small appliance 3,000 VA; laundry 1,500 VA; bath 1,500 VA; bedroom 1,200 VA; HVAC 2,400 VA; total 10,800 VA; demand 45 A at 240 V. Existing service 100 A; new subpanel 60 A. Verify with the actual service calculation.
P1.0: WC 3", lav 1-1/2", shower 2"; 2" vent; 1/2" supplies; cleanout; access panels.
M1.0: equipment, supply/return, bath exhaust, fresh air, condensate. Manual J attached.
| Item | Value |
|---|---|
| Area | 400 SF |
| Cooling | 12,000 BTU/hr |
| Heating | 5 kW |
| Supply / return | 200 CFM / 200 CFM |
| Bath exhaust | 50 CFM to exterior |
LS1.0: EERO 5.7 SF, 24" × 20", sill ≤44"; stair 36" clear, 10" tread, 7-3/4" riser; guard 36"; smoke/CO.
| Inspection | When | Call |
|---|---|---|
| Pre-construction / permit posting | Before work | [ ] |
| Footing/foundation | Before concrete | [ ] |
| Framing | Before covering | [ ] |
| Electrical rough | Before insulation | [ ] |
| Plumbing rough | Before insulation | [ ] |
| HVAC rough | Before insulation | [ ] |
| Insulation / air sealing | Before drywall | [ ] |
| Final building / electrical / plumbing / HVAC | At completion | [ ] |
| Smoke/CO | At final | [ ] |
| [ ] | Building permit application, signed by owner |
| [ ] | Owner-builder affidavit |
| [ ] | Unpaid family labor acknowledgment (recommended) |
| [ ] | Contractor registration / insurance / BWC for paid subs |
| [ ] | Zoning envelope worksheet |
| [ ] | ABR approval letter |
| [ ] | BZA variance approval (if required) |
| [ ] | Historic/HP approval (if applicable) |
| [ ] | Plan set A0–LS1 |
| [ ] | Sealed structural calculations and letter |
| [ ] | Electrical load calculation / panel schedule |
| [ ] | Plumbing plan / riser |
| [ ] | HVAC Manual J / duct layout |
| [ ] | Energy compliance |
| [ ] | Survey / site plan |
| [ ] | Fees |
Lakewood publishes ABR agendas and minutes, which often include site plans, elevations, and photos. It does not publish the full building-permit set with sealed architectural, structural, electrical, plumbing, and HVAC drawings. To see a real full set for a similar project, request the permit file for a specific address through the Lakewood Building Department or review the plans at the counter with the owner’s permission. The drawings on this page are representative, not a real applicant’s sealed set.